My Techfocus

First time here? Sign Up


Salicru SPS 1500 ADV RT2 Uninterruptible Power Systems (UPS)

  • NG # 00267-HW-SAL-067

Manufactured by:

This seller generally responds in under 48 hours

The Salicru SPS 1500 ADV RT2 is a robust Uninterruptible Power System (UPS) engineered with 1500 VA line-interactive sine-wave technology to ensure stable and reliable power protection for entry-level servers, networking equipment, and critical IT systems. 

Specification

TECHNOLOGYLine-interactive
FORMATConvertible tower/rack (2U)
Rated voltage208 / 220 / 230 / 240 V
Voltage range 100% load170 ÷ 280 V
StabiliserAVR (Buck & Boost)
Rated frequency50 / 60 Hz (auto-detection)
Frequency range±5 Hz
Auto~detection of frequencyYes
ProtectionFuse (800/1100) or resettable thermal cutoff (1500/2000/3000)
Power factor0.9
Rated voltage208 / 220 / 230 / 240 V
Voltage accuracy (battery mode)±1.5%
Power (VA/W)1500 / 1350
Total harmonic distortion (THDv)< 2% linear load / < 5% non-linear load
Waveform (battery mode)Pure sine wave
Frequency50/60 Hz (same as input)
Frequency accuracy (battery mode)±0.1Hz
Admissible overloads in battery mode< 120% off at 1 min / < 150% off at 10 s
Admissible overloads in-line mode< 120% off at 5 min / < 150% off at 10 s / >150 %: 1 s
Socket typeIEC
No. Of sockets8
Programmable socketsYes, for critical / non-critical loads (4/4)
Battery typePb-Ca sealed, AGM, maintenance-free
Charge typeI/U (constant current/constant voltage)
Recharge time4 hours to 90%
Battery testAutomatic on every start + one x week
Temperature voltage compensationYes
PortsRS-232/USB-HID
Intelligent slotSlot for SNMP/potential-free contacts/ MODBUS
Monitoring softwareFor Windows, Linux and Mac
TypeLCD + keypad
ValuesVoltage, power and input and output frequency / Battery voltage / % battery charge / % load / Operating mode / Fault / Discharge time / Mute
Operating modesNormal / Stabilisation (AVR) / Battery / Fault
AlarmOutput battery mode, polarity, low battery (back up time), charger failure and overload
AudibleEvery 10 s for battery operation. Every 2 s for low battery / Polarity. Every 1 s for overcharge. Continuous for fault.
FailureDisplay LCD
Cold start (start-up from batteries)Yes
Emergency stop (EPO)Yes
ADSL/fax/modem transient protector
Yes
Green-functionYes, automatic stop in battery mode with load <5%
Smart fan speedYes, smart control of fan speed
Site wiring faultYes, error detection of phase-neutral rotation and/or absence of earth
Operating temperature0º C ÷ 40º C
Relative humidityUp to 95%, non-condensing
Maximum operating altitude2,400 masl (power degradation up to 5,000 m)
Acoustic noise at 1 meter< 45dB
SafetyEN IEC 62040-1
Electromagnetic compatibility (EMC)EN IEC 62040-2 (C2)
OperationEN IEC 62040-3
Corporate certificationISO 9001, ISO 14001, ISO 45001
Depth (mm)510
Width (mm)438
Height (mm)88
Weight (kg)19.5

Description

Designed with a flexible tower/rack format, it offers adaptable installation options to meet diverse infrastructure requirements. This UPS delivers effective safeguarding against power fluctuations, surges, and outages, ensuring uninterrupted operation and data protection for essential systems. With its line-interactive design, the SPS 1500 ADV RT2 enhances energy efficiency and voltage regulation, while its pure sine-wave output ensures seamless compatibility with sensitive electronic devices. Ideal for small to medium-scale IT environments, office networks, and business-critical applications, it provides dependable backup power with advanced performance and reliability.