Dräger Polytron 5200 CAT
007003-HW-Dräger-003
Overview
A cost-effective, explosion-proof transmitter for flammable gas detection that uses a catalytic-bead DrägerSensor® Ex and provides a standard 3-wire 4–20 mA analogue output for reliable integration with most control systems.
| Type | Transmitter |
|---|---|
| Measuring Principle | Catalytic Bead Sensor |
| Response time | |
| Cable entry | M20 or 3/4" NPT |
| Display | Yes |
| Intrinsic Safety | No |
| Flameproof | Yes |
| Increased Safety | Yes |
| SIL | SIL 2 (IEC 61508-2) |
| 4-20 mA | Yes |
| Bus | No |
| HART® | No |
| Wireless | No |
Technical Data
| Power Supply | 10 to 30 V, 3-wire |
|---|---|
| Temperature (operation) | -40°C - 80°C |
| Humidity | 0 to 100 % r.h., non-condensing |
| Pressure (hPa) | 700 - 1300 |
| Dimensions (H Ă— W Ă— D) | 28x15x13 cm |
| Weight | 4 Kg |
| Housing Material | Epoxy coated copper-free aluminum or stainless steel SS 316L |
| Degree of protection (IP class) | IP65/66/67 |
Approvals
| ATEX | Yes |
|---|---|
| IECEx | Yes |
| UL | Yes |
| CSA | Yes |
| CE marking | Yes |
| GOST (EAC) | Yes |
| Performance approval | Yes |
| Shipping approval | No |
| FM | No |
This transmitter is designed for reliable, continuous detection of combustible gases in hazardous locations. Housed in an explosion-proof enclosure, it protects electronics and the sensor assembly from ignition sources while the catalytic-bead DrägerSensor® Ex provides proven, fast response to hydrocarbon vapours. With a 3-wire 4–20 mA output and simple wiring, the device plugs into PLCs, DCS, fire panels, or standalone controllers without special interfaces, making it an economical choice for refineries, chemical plants, storage areas and confined spaces.